b) In a Power Share application where the New Power System is taking only part of
the load (operating continuously at the current level equivalent to the
programmed “PS Initial Capacity Limit” percentage) and the rectifiers in the
Existing Power System are taking the rest of the load, use an external dry load
bank of sufficient capacity to increase the load in order to exceed the total
capacity of the rectifiers in the Existing Power System (or shut down some of the
rectifiers in the Existing Power System if the capacity of the external dry load
bank is not sufficient).
1) Verify that the New Power System starts taking the additional load as soon
as the total capacity of the rectifiers in the Existing Power System is
exceeded.