1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key. The FUNCTION MENU is displayed.
or
In the MAIN ALARM MENU, repeatedly press and release the FUNCTION
SELECT DOWN arrow key until "GO TO FUNCTION MENU" is displayed. Press
and release the FUNCTION SET ENTER key. The FUNCTION MENU is
displayed.
Note: In the following step, if "TEST/EQ MODE ACTIVE. SET FLOAT?" is
displayed, the system is already operating in the test/equalize mode. In this
case, DO NOT perform steps 2) through 4), proceed with step 5).
2) Press and release the FUNCTION SELECT DOWN arrow key to display "FLOAT
MODE IS ACTIVE. SET TEST/EQ?".
3) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
4) "ARE YOU SURE?" is displayed. Press and release the FUNCTION SET YES
(+) key.
5) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.
Returning to Float Mode: The system automatically returns to float mode when the
"timed test/equalize period" expires.
Note: Navigating to "END TEST/EQUALIZE IN hhh.hh HOURS" of the MCA configure
menu displays the hours remaining in the timed test/equalize period.
Note: Timed test/equalize is canceled and the system is placed in the float mode if any
of the following occurs.
1) Manually placing the system in the float mode by navigating to and activating
"TEST/EQ MODE ACTIVE. SET FLOAT?" menu item in the MCA function
menu, as previously described in this chapter.
2) Resetting the "MANUAL TEST/EQUALIZE = hh HOURS" value in the MCA
configure menu when "END TEST/EQUALIZE IN hhh.hh HOURS" is being
displayed, as described in the previous procedure
3) Applying an external test/equalize signal as described in the next procedure.