User's Manual

Table Of Contents
User Instructions Section 5877
Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B) Issue AQ, January 15, 2013
Chapter 3. System Operating Procedures Page 3-11
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
8) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.
Placing the System into Test/Equalize Mode: Manually place the system into
test/equalize mode by navigating to and activating the "FLOAT MODE IS ACTIVE. SET
TEST/EQ?" menu item in the MCA function menu. The system is placed in the
test/equalize mode and must be manually placed back to the float mode. A step-by-step
procedure is provided next.
1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key. The FUNCTION MENU is displayed.
or
In the MAIN ALARM MENU, repeatedly press and release the FUNCTION
SELECT DOWN arrow key until "GO TO FUNCTION MENU" is displayed. Press
and release the FUNCTION SET ENTER key. The FUNCTION MENU is
displayed.
Note: In the following step, if "TEST/EQ MODE ACTIVE. SET FLOAT?" is
displayed, the system is already operating in the test/equalize mode. In this
case, DO NOT perform steps 2) through 4), proceed with step 5).
2) Press and release the FUNCTION SELECT DOWN arrow key to display "FLOAT
MODE IS ACTIVE. SET TEST/EQ?".
3) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
4) "ARE YOU SURE?" is displayed. Press and release the FUNCTION SET YES
(+) key.
5) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.
Returning to Float Mode: To return to float mode, navigate to and activate the
"TEST/EQ MODE ACTIVE. SET FLOAT?" menu item in the MCA function menu, as
previously described in this chapter.