Page 3-10 Chapter 3. System Operating Procedures
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Placing the System into the Test/Equalize Mode of Operation
Warning: Do not supply equalize output voltage for a longer period than
necessary. Prolonged higher battery charge voltage overcharges the
battery cells and reduces battery life.
Note: Test/Equalize Mode requires Power Share to be turned off.
There are four methods of placing the system from the float mode to the test/equalize
mode.
Method 1 (Manual Test/Equalize) Procedure
In this method, a user manually places the system into the test/equalize mode via the
MCA Control Panel. A user must manually return the system to the float mode via the
MCA Control Panel. Follow the procedures described below.
Setting for Manual Test/Equalize: Set the "MANUAL TEST/EQUALIZE = hh HOURS"
menu item in the MCA configure menu to below 0. The display changes to
"TEST/EQUALIZE STOP IS MANUAL" to indicate manual test/equalize mode is set. A
step-by-step procedure is provided next.
1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key. The FUNCTION MENU is displayed.
or
In the MAIN ALARM MENU, repeatedly press and release the FUNCTION
SELECT DOWN arrow key until "GO TO FUNCTION MENU" is displayed. Press
and release the FUNCTION SET ENTER key. The FUNCTION MENU is
displayed.
2) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
"CHANGE CONFIGURATION PARAMETERS" is displayed. Press and release
the FUNCTION SET ENTER key.
3) Press and release the FUNCTION SELECT DOWN arrow key to display
"MANUAL TEST/EQUALIZE = hh HOURS" or "TEST/EQUALIZE STOP IS
MANUAL" is displayed.
Note: If "TEST/EQUALIZE STOP IS MANUAL" is displayed, the system is
already set for manual test/equalize. In this case, proceed with step 8).
Note: If "END TEST/EQUALIZE IN hhh.hh HOURS" is displayed, the system is
set for manually initiated timed test/equalize, and a timed test/equalize is
in progress. In this case, you can proceed with steps 4) through 7) to
cancel the timed test/equalize in progress and change the current setting,
or proceed with step 8) to proceed with the timed test/equalize in progress
and make no changes.
4) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
5) Press the FUNCTION SET NO / - key to scroll the displayed value towards 0.
Release the key when "TEST/EQUALIZE STOP IS MANUAL" is displayed. This
indicates the manually initiated timed test/equalize feature is disabled and the
system must be manually returned to the float mode if placed in the test/equalize
mode.
6) Press and release the FUNCTION SET ENTER key.
7) “ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.