RESTARTING PROCEDURES WHEN RECTIFIER IS
AUTOMATICALLY OR MANUALLY INHIBITED, SHUT DOWN, OR
LOCKED OUT
Rectifier High Voltage Shutdown Lockout
Place the Standby/Operate switch to the "standby" position, and then back to the I
"operate" position.
Rectifier Emergency Shutdown and Fire Alarm Disconnect
Remove the emergency shutdown and fire alarm disconnect signal, and on each Rectifier
place the Standby/Operate switch to the "standby" position and then back to the I
"operate" position.
Remote On/Off (TR)
Remove the remote on/off (TR) signal from the respective Rectifier. The signal can
originate from the LMS (if installed), or via the local MCA Control Panel.
OUTPUT VOLTAGE MODE OF OPERATION SELECTION
Placing the System into the Float Mode of Operation
Manually place the system into float mode by navigating to and activating the "TEST/EQ
MODE ACTIVE. SET FLOAT?" menu item in the MCA function menu. A step-by-step
procedure is provided next.
1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key. The FUNCTION MENU is displayed.
or
In the MAIN ALARM MENU, repeatedly press and release the FUNCTION
SELECT DOWN arrow key until "GO TO FUNCTION MENU" is displayed. Press
and release the FUNCTION SET ENTER key. The FUNCTION MENU is
displayed.
Note: In the following step, if "FLOAT MODE IS ACTIVE. SET TEST/EQ?" is
displayed, the system is already operating in the float mode. In this case, DO
NOT perform steps 2) through 4), proceed with step 5).
2) Press and release the FUNCTION SELECT DOWN arrow key to display
"TEST/EQ MODE ACTIVE. SET FLOAT?".
3) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
4) "ARE YOU SURE?" is displayed. Press and release the FUNCTION SET YES
(+) key.
5) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.