Installation Instructions

Section 5876 Installation Instructions
Issue AT, April 26, 2013 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 2-64 Chapter 2. Placing the Bays and Installing Internal/External Busbars
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 2-48
Power/Distribution Bay External Top-Mount Vertical Busbar Assembly (P/N 554874)
Assembly Procedure Step 4
Note: Concave side of Belleville washer faces
busbar; convex side faces bolt head.
(6) 3/8-16 x 1-1/4” Bolt, P/N 227646800 Torque to 180 in-lbs.
(6) 3/8” Belleville Washer, P/N 214825000
(6) 3/8” Flat Washer, P/N 214204100
Note: Apply electrical anti-oxidation compound
to busbar mating surfaces.
(1) Vertical Landing Negative Busbar, P/N 548000
Rear Top
of Bay
Assembled
View
STEP 4
Install “Vertical Landing Negative Busbar”
onto “Main Negative Busbar”.