Installation Instructions
Section 5876 Installation Instructions
Issue AT, April 26, 2013 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 2-52 Chapter 2. Placing the Bays and Installing Internal/External Busbars
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 2-37
Power/Distribution Bay Load Return Lug Extension Busbar Assembly (P/N 514543)
Assembly Procedure Step 1A
STEP 1A
Install "Load Return Lug Extension Busbar"
(List 1 and 11 Bays).
Remove any
previously installed
bolts from these
four locations
Note: Apply Electrical Anti-Oxidation
Compound to all Busbar
Mating Surfaces.
(1*) Busbar, P/N 514542
(8*) 3/8-16 x 3" Bolt, P/N 227647800
(8*) 3/8" Flat Washer, P/N 214204100
(hardened, thicker than other Kit
supplied 3/8" flat washer)
(8*) 3/8" Belleville Washer, P/N 214825000
(8*) 3/8-16 Nut, P/N 228567100
* Quantities are per Kit,
two Kits shown in Illustrations.
Previously Assembled
Kit P/N 514688 or 514689
Previously Assembled
Kit P/N 554873
Note: Concave Side of Belleville
Washer Faces Busbar,
Convex Side Faces Bolt Head.
Front Top
of Bay
Assembled
View
Torque to 180 in-lbs.