Installation Instructions

Installation Instructions Section 5876
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AT, April 26, 2013
Chapter 2. Placing the Bays and Installing Internal/External Busbars Page 2-19
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
INSTALLING POWER/DISTRIBUTION BAY TO
POWER/DISTRIBUTION BAY NEGATIVE
AND POSITIVE BUSBAR LINKS
Note: Refer to the next procedure to connect the newer style bay to an existing older
style bay.
Note: Apply electrical anti-oxidation compound to mating surfaces of busbars before
connecting together.
Procedure
1) Refer to Figure 2-10 or Figure 2-11 and install the "Negative Busbar Link"
between the "Negative Side" of one bay and the "Negative Side" of the adjacent
bay. Use the supplied 3/8-16 x 1-1/2" bolts and hardware. Hardware build-up is:
Bolt, Belleville Lock Washer, Belleville Lock Washer (concave side of Belleville
lock washers face each other), Hardened Flat Washer. Torque to 180 in-lbs.
2) Refer to Figure 2-10 or Figure 2-11 and install the "Positive Busbar Link"
between the "Positive Side" of one bay and the "Positive Side" of the adjacent
bay. Use the supplied 3/8-16 x 1-1/2" bolts and hardware. Hardware build-up is:
Bolt, Belleville Lock Washer, Belleville Lock Washer (concave side of Belleville
lock washers face each other), Hardened Flat Washer. Torque to 180 in-lbs.
3) For bays with PDSCs, the busbar link cover shield is installed after all mounting
and electrical connection procedures are completed.