Installation Instructions
Section 5876 Installation Instructions
Issue AT, April 26, 2013 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 5-36 Chapter 5. Installing the Rectifiers and Initially Starting the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
a) Requirement: The bay's "Bay Alarm" indicator goes red.
b) Requirement: The distribution panel's "CBA/FA" indicator goes red.
c) Requirement: MCA “MAJOR” indicator flashes red.
d) Requirement: MCA displays 1 SYSTEM BREAKER OR FUSE ALARM.
e) Requirement: External alarms activate (if configured).
6) Place the circuit breaker back to the ON position.
a) Requirement: The bay's "Bay Alarm" indicator goes out.
b) Requirement: The distribution panel's "CBA/FA" indicator goes out.
c) Requirement: MCA “MAJOR” indicator goes out.
d) Requirement: MCA displays SYSTEM OK message.
e) Requirement: External alarms reset (if configured).
7) Perform steps 5) and 6) for each remaining distribution circuit breaker located in
the system.
Checking Metering Functions
Procedure
1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key.
2) VIEW THE SYSTEM MEASUREMENTS is displayed. Press and release the
FUNCTION SET ENTER key.
a) Requirement: System output sense voltage is displayed.
3) Press and release the FUNCTION SET ENTER key.
a) Requirement: External sense input voltage is displayed.
4) Repeatedly press and release the FUNCTION SELECT DOWN arrow key to
display the sense voltage reported by each bay's router.
a) Requirement: As the FUNCTION SELECT DOWN arrow key is pressed
and released, router sense voltages are displayed. When all router's are
cycled through, GO TO MEASUREMENT MENU is displayed.
5) With GO TO MEASUREMENT MENU being displayed, press and release the
FUNCTION SET ENTER key.
6) Press and release the FUNCTION SELECT DOWN arrow key.
a) Requirement: Total distribution load current is displayed.
7) Press and release the FUNCTION SET ENTER key.
a) Requirement: The load current of the first Distribution Panel is displayed.
8) Press and release the FUNCTION SET ENTER key.
a) Requirement: The load current of the first Distribution Device in the
Distribution Panel is displayed.
9) Repeatedly press and release the FUNCTION SELECT DOWN arrow key to
display individual load currents through the remaining Distribution Devices.
a) Requirement: As the FUNCTION SELECT DOWN arrow key is pressed
and released, load currents through the remaining Distribution Devices are