Installation Instructions

Section 5876 Installation Instructions
Issue AT, April 26, 2013 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 5-22 Chapter 5. Installing the Rectifiers and Initially Starting the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
6) TIME PER FUNCTION = hh:mm:ss is displayed. Repeatedly press and release
the FUNCTION SELECT DOWN and UP arrow keys to select a time period for
each Relay Function Channel test or to display TIME PER FUNCTION NO
TIMEOUT.
7) Press and release the FUNCTION SET ENTER key.
8) Press the UP and DOWN ARROW keys to select either AUTOMATICALLY TEST
ALL FUNCTIONS (to test all Relay Function Channels) or TEST RELAY
FUNCTION A# (to test an individual Relay Function Channel).
9) Press and release the FUNCTION SET ENTER key.
10) “ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
11) The Relay Function being tested and the remaining time are displayed. Check
your external alarms for proper operation.
12) To terminate the test, press and release the ALARM CUTOFF and FUNCTION
SET ENTER keys simultaneously until STOP RELAY FUNCTION TEST is
displayed.
13) “ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
Setting MCA I/O Circuit Card Parameters
Procedure
1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key.
2) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
CHANGE CONFIGURATION PARAMETERS is displayed.
3) Press and release the FUNCTION SET ENTER key.
4) CHANGE I/O BOARD PARAMETERS is displayed. Press and release the
FUNCTION SET ENTER key.
5) Navigate the I/O BOARD CONFIGURATION MENU to set…
any analog input to show up in the DISTRIBUTION or AUXILIARY menus,
any analog input scale factor,
any analog output scale factor,
any binary input alarm state (open or close).
Note: If a binary input alarms, the MCA displays a "Binary Input Customer Text
Message" in the I/O Board Alarm Detail Message. If you wish to change
the default message, refer to the "SYSTEM OPERATING
PROCEDURES" chapter in Section 5877.
6) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.
Checking Manual Test/Equalize
and Manually Initiated Timed Test/Equalize
Note: Test/Equalize Mode requires Power Share to be turned off.
Procedure
1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key.