Installation Instructions
Section 5876 Installation Instructions
Issue AT, April 26, 2013 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 5-16 Chapter 5. Installing the Rectifiers and Initially Starting the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
DISTRIBUTION GROUP B
= aaaaA
Allows you to change the
Distribution Group B Load Current
Alarm set point.
HIGH TEMPERATURE #1
= ttt°C/F
or
NO HIGH TEMPERATURE
#1 ALARM
Allows you to change the High
Temperature #1 Alarm set point, or
disable the alarm.
Note: To disable the feature, press
YES / + / i when in the change
setting mode to scroll to NO HIGH
TEMPERATURE #1 ALARM
(displayed when you scroll up to
"100°C").
HIGH TEMPERATURE #2
= ttt°C/F
or
NO HIGH TEMPERATURE
#2 ALARM
Allows you to change the High
Temperature #2 Alarm set point, or
disable the alarm.
Note: To disable the feature, press
YES / + / i when in the change
setting mode to scroll to NO HIGH
TEMPERATURE #2 ALARM
(displayed when you scroll up to
"100°C").
LOW TEMPERATURE #1
= ttt°C/F
or
NO LOW TEMPERATURE
#1 ALARM
Allows you to change the Low
Temperature #1 Alarm set point, or
disable the alarm.
Note: To disable the feature, press
NO / - when in the change setting
mode to scroll to NO LOW
TEMPERATURE #1 ALARM
(displayed when you scroll down to
"-50°C").
LOW TEMPERATURE #2
= ttt°C/F
or
NO LOW TEMPERATURE
#2 ALARM
Allows you to change the Low
Temperature #2 Alarm set point, or
disable the alarm.
Note: To disable the feature, press
NO / - when in the change setting
mode to scroll to NO LOW
TEMPERATURE #2 ALARM
(displayed when you scroll down to
"-50°C").
AUDIBLE SILENT TIME
= mm MINUTES
or
AUDIBLE ALARMS STAY
SILENCED
Allows you to enable the MCA
Audible Alarm feature and set the
Audible Alarm Cutoff Reset Time
Period set point, or disable the
feature.
Note: To disable the feature, press
NO / - when in the change setting
mode to scroll to AUDIBLE
ALARMS STAY SILENCED
(displayed when you scroll down to
"zero minutes").