Installation Instructions
Installation Instructions Section 5876
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AT, April 26, 2013
Chapter 4. Making Electrical Connections Page 4-59
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Power Only Bay
Located on the rear top of each bay are studs (3/8-16 on 1" centers). Attach battery
leads to these using customer supplied two-hole lugs and mounting hardware. When
lugs are secured using 3/8 inch bolts; recommended torque is 180 in-lbs when a
Belleville lock washer is used, and 300 in-lbs when a standard flat washer and lock
washer are used.
Refer to Figure 4-24 for battery landing locations.
Figure 4-24
Battery Connection to Rear of Power Only Bay
POSITIVE BATTERY
(GROUND RETURN)
NEGATIVE BATTERY
(SUPPLY -48V)
2.000"
1.000"
1.000"
3/8-16 Stud
(40)
Rear View
Power Only Bays