Section 5876 Installation Instructions
Issue AT, April 26, 2013 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 4-38 Chapter 4. Making Electrical Connections
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Distribution Only Bay
To 218 Circuit Breakers and TPL Fuses
Each Distribution Bay has four (4) distribution buses. Each distribution bus has twelve
(12) fuse/circuit breaker device mounting positions. Note that the various fuse/circuit
breaker devices require different number of mounting positions. The load side of each
fuse/circuit breaker mounting position is bused to the rear of the bay. Each fuse/circuit
breaker device requires a load lug adapter plate kit that mounts to the appropriate load
side busbars at the rear of the bay (except 1-pole devices). Load return leads are
terminated outside the bay to the optional external ground busbar mounted on top of the
bay.
Refer to Figure 4-12 for load lug landing locations.
When lugs are secured using 3/8 inch hardware, recommended torque is 180 in-lbs when
a Belleville lock washer is used, and 300 in-lbs when a standard flat washer and lock
washer are used.
Connect load leads to the respective load busbar located at the rear of the bay. These
busbars are provided with 3/8” clearance holes on 1 inch centers for installation of
customer provided two hole lugs. Note that for distribution devices that require more than
one distribution mounting positions, lug adapter kits are furnished, as ordered. The kit
supplied lug adapters are provided with 3/8 clearance holes on 1 inch centers for
installation of customer provided two hole lugs. The kits also contains 3/8" mounting
hardware.
Load Side
Load return leads are terminated outside the bay to customer provided return busbars.
Load Return Side