Installing Rectifiers into Power/Distribution and Power Only Bays
Install Rectifiers from top to bottom, starting with the top most mounting position. (In the MCA display messages,
the Rectifiers are numbered from 1 to 10, starting with the top most position.) The Rectifier weighs approximately
40 lbs.
Procedure
1) Remove the blank panel from the Rectifier mounting position. Save this panel. The panel must be re-
installed if a Rectifier is removed.
Note: In the next step, a safety latch is present on the left-hand (as viewed from the front) side panel of each
Rectifier. The latch is designed to prevent the Rectifier from inadvertently being removed completely
from the Bay once it has been installed. It should not be necessary to depress the safety latch release
when installing the Rectifier.
2) Install the Rectifier into the bay by sliding it evenly into its mounting position. Secure the Rectifier to the
bay by tightening the captive fasteners on the Rectifier.
3) Perform steps 1) and 2) for each Rectifier to be installed.