AC Input Connections to Lists 2 and 12 Power/Distribution Bays (with PDSC)
(One AC Feed)
A B C
Rear View
Optional Bolt-On PCU
AC Input Service Cabinet
Ensure that each bay is wired into the PDSC as detailed in
"Chapter 2. Placing the Bays and Installing Internal/External Busbars".
Frame Ground Nuts
to Secure Lugs and Lug
Mounting Hardware
(3/8-16 on 1" Centers)
(Accessed from Inside Cabinet)
3/8-16 x 1.25 Studs (6) on 1" Centers
for Installation of Customer Provided Lugs
Recm. Torque
3/8" Hardware
using Belleville
Lock Washer
180 in-lbs, using
flat washer and
lock washer
300 in-lbs.
480VAC (List A) or 208VAC (List B), 3 Phase, 60Hz
Single Feed