Installation Guide

Section 5957 Installation Guide
Issue AM, March 26, 2014 Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B)
Page 40
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Power/Distribution Bay
External Top-Mount Vertical Battery Input Busbar Assembly (P/N 554874)
Assembly Procedure Step 3
(1) Main Negative Busbar, P/N 554875
Note: Apply Electrical Anti-Oxidation Compound
to busbar mating services.
Note: Concave side of Belleville washer faces
busbar; convex side faces hex nut.
(8) 3/8Flat Washer, P/N 214204100
(8) 3/8Belleville Washer, P/N 214825000
(8) 3/8-16 Hex Nut, P/N 228567100 Hand-tighten only.
Rear Top
of Bay
Assembled
View
STEP 3
Install Main Negative Busbaronto Bay
Negative Busbar.
Mount 554876 to the 554875.
Hardware:
214204100 (4)
214825000 (4)
228567100 (4)