Data Sheet
2 004D-NS802 / 0413
NetSure
™
802 Series
Centralized Architecture:
Stand-Alone Power and
Distribution Bays
The NetSure
™
802 system’s new, individual
power bays and distribution bays can be
paired with high-efficiency eSure
™
rectifi-
ers and configured to meet any application
requirement, including ferro retrofits.
Power bays are available with individual AC
feeds or may be bulk fed using an existing
power distribution service cabinet (PDSC)
by simply rerouting existing cabling and
using existing breakers—with a separate
breaker for each rectifier. That means
shutting down a breaker to service or
replace a rectifier impacts only that rectifi-
er. Web pages in the LMS1000 monitoring
system have been upgraded to offer new
features. There are three power bays to
choose from, and the bays can be mixed
and matched to suit specific applications.
Those three options are:
n Bulk Feed (Main Bay = 58214000004,
Sup Bay = 58214000014)
n 400A Ferro Retrofit (Main Bay =
58214000003, Sup Bay = 58214000013)
n 200A Ferro Retrofit (Main Bay =
58214000005, Sup Bay = 58214000015)
Distributed Architecture:
Combination Bays
The proven NetSure
™
802 combination
bays provide power and distribution in the
same bay, retaining the internal busses
originally introduced in this product line.
These bays also may be configured with
new high-efficiency eSure
™
rectifiers and
are available with individual AC feeds
(480V or 208V options) or may be bulk fed
using Emerson’s side-by-side PDSC. The
web interface for the LMS1000 monitoring
system has been upgraded for ease of use.
Ferro Retrofits
Emerson Network Power’s NetSure
™
802
power bays are set up to allow reuse of
existing AC infrastructure for 200 and 400
amp ferro rectifiers—the most popular fer-
ros still in service. These bays, with each
rectifier assigned to its own breaker, are
useful for deployments with existing
PDSCs or when the preference is to have
the AC circuit breakers remote from the
system. Ferro retrofit applications also
allow reuse of existing main battery termi-
nation bars.
NetSure
™
802 Combination BayNetSure
™
802 Power Bay 200A Ferro Retrofit
Power Bay
400A Ferro Retrofit
Power Bay
Distribution Options
Distribution Element Combination Bay Distribution Bay
TPS/TLS Fuses or Bullet Circuit Breakers 48 24
100-250A Circuit Breakers 24 48
300-400A Circuit Breakers 12 24
70-600A TPL Fuses 12 24
450-600A Circuit Breakers 8 16
800A TPL Fuses 8 16
800A Circuit Breakers 4* 8*
* For each 800 Amp circuit breaker deployed there is space on the bus for one two-pole or two single-pole circuit breakers.