Step 1. Select System Frame(s), Main Bay or Supplemental Bay
Select one, quantity of one per system.
List
Number
Emerson
Part Number
Description
Qty.
Notes
List 1 58214000001
Main power/distribution frame, equip for
individual AC feed per rectifier
(1) Main frame type required per system.
Maximum of 10 rectifiers/bay.
List 2 58214000002
Main power/distribution frame, equip for bulk
AC feed per frame
Must select AC service cabinet option in Step 5.
List 3* 58214000003
Main power bay frame, 5 discrete AC inputs
per bay (5 feed) for 400 A ferro retrofit
application
(1) Main frame type required per system.
Maximum of 10 rectifiers/bay.
List 4* 58214000004
Main power bay frame, 2 discrete AC inputs
per bay (2 feed)
(1) Main frame type required per system.
Maximum of 10 rectifiers/bay.
List 5* 58214000005
Main power bay frame, individual AC inputs
per rectifier (10 feed) for 200 A Ferro retrofit
applications or direct feed from existing AC
PDSC
(1) Main frame type required per system.
Maximum of 10 rectifiers/bay.
* Must be used with external main battery termination bars.
Select quantity as needed per system.
List
Number
Emerson
Part Number
Description
Qty.
Notes
List 11 58214000011
Secondary power/distribution frame, equip
for individual AC feed per rectifier
Order as required. Maximum of 10 rectifiers/bay.
System can support up to (9) secondary frames as needed.
List 12 58214000012
Secondary power/distribution frame, equip
for bulk AC feed per frame
Must select AC service cabinet option in Step 5. Order as
required. Maximum of 10 rectifiers/bay. System can support up
to (9) secondary frames as needed.
List 13* 58214000013
Secondary power bay frame, 5 discrete AC
inputs per bay (5 feed) for 400 A ferro retrofit
application
Order as required. Maximum of 10 rectifiers/bay.
System can support up to (9) secondary frames as needed.
List 14* 58214000014
Secondary power bay frame, 2 discrete AC
inputs per bay (2 feed)
Order as required. Maximum of 10 rectifiers/bay.
System can support up to (9) secondary frames as needed.
List 15* 58214000015
Secondary power bay frame, individual AC
inputs per rectifier (10 feed) for 200 A Ferro
retrofit applications or direct feed from exist-
ing AC PDSC
Order as required. Maximum of 10 rectifiers/bay.
System can support up to (9) secondary frames as needed.
* Must be used with external main battery termination bars.
Step 2. Optional - Select Distribution Frame
Select quantity as needed if applicable.
List
Number
Emerson
Part Number
Description
Qty.
Notes
List 16* 58214000016 Distribution frame, no rectification
Order as required. System can support up to (5) distribution
frames as needed.
* Must be used with external main battery termination bars.
Step 3. Select Input Voltage Source (AC Input Source)
Select one, quantity of one.
List
Number
Emerson
Part Number
Description
Qty.
Rack
Space
List 0A 5821400000A 480 VAC, 3 phase input (4-wire circuit)
List 0B 5821400000B 208 VAC, 3 phase input (4-wire circuit)
NetSure
™
802 Series
DC Power System