Updating the Inventory after Changes
to the System Have Been Made
When an inventory item is removed from the system, an alarm will be reported until the
following procedure is performed.
Example, if a Rectifier is removed from the system, the Rectifier will not be removed from
the MCA's inventory until "VIEW THE SYSTEM INVENTORY" is entered and the
"UPDATE THE INVENTORY" operation is completed.
Procedure
1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key. The FUNCTION MENU is displayed.
or
In the MAIN ALARM MENU, repeatedly press and release the FUNCTION
SELECT DOWN arrow key until "GO TO FUNCTION MENU" is displayed. Press
and release the FUNCTION SET ENTER key. The FUNCTION MENU is
displayed.
2) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
"VIEW THE SYSTEM INVENTORY" is displayed.
3) Press and release the FUNCTION SET ENTER key.
4) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
"UPDATE THE INVENTORY" is displayed.
5) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
6) “ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
7) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.