Application Guide

Table Of Contents
Section 5877 User Instructions
Issue AQ, January 15, 2013 Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B)
Page 4-12 Chapter 4. MCA System Adjustments
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
ADJUSTING DISTRIBUTION GROUP A LOAD ALARM
1) All controls are located on the MCA Interface Pad.
2) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key. The FUNCTION MENU is displayed.
or
In the MAIN ALARM MENU, repeatedly press and release the FUNCTION
SELECT DOWN arrow key until "GO TO FUNCTION MENU" is displayed. Press
and release the FUNCTION SET ENTER key. The FUNCTION MENU is
displayed.
3) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
"ADJUST THE ALARM SETPOINTS" is displayed.
4) Press and release the FUNCTION SET ENTER key.
5) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
"DISTRIBUTION GROUP A = aaaaaA" is displayed.
6) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
7) Observe the value displayed. This is the Group A Load Current alarm setting.
To change this value, press and hold the FUNCTION SET YES (+) or NO (-) key.
Release the key when the desired value is displayed.
8) With the desired Group A Load Current alarm value being displayed, press and
release the FUNCTION SET ENTER key.
9) “ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
Note: The Group A Load Current alarm value will not be changed and the
adjustment mode will be exited if the FUNCTION SET YES (+) key is not
pressed within 10 seconds of the “ARE YOU SURE?” prompt.
10) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.