Issue AQ, January 15, 2013 Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B)
Page 3-26 Chapter 3. System Operating Procedures
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
6) Continue with the next procedure.
Setting the Alternate Current Limit Initial Capacity Limit
1) From the previous procedure, press and release the FUNCTION SELECT
DOWN arrow key to display "ALTERNATE CURRENT LIMIT = ##%".
2) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously.
3) Press and hold the FUNCTION SET YES (+) or NO (-) key to change this setting
as required. Release the key when the desired value is displayed.
Note: Enter the percentage value of the total PCU output capacity at which the
system will current limit when the “Alternate Current Limit Input” becomes
active.
(Adjustable from 10% to 110%, factory set at 100%.)
4) With the desired value being displayed, press and release the FUNCTION SET
ENTER key.
5) “ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
6) Press and release the FUNCTION SET YES (+) and NO (-) keys simultaneously,
to return to the beginning of the MCA menu tree.