Application Guide

Installation Instructions Section 5876
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AT, April 26, 2013
Chapter 3. Installing Distribution Devices and MCA/LMS Circuit Cards Page 3-3
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Installing TLS/TPS Fuses
Refer to Figure 3-7 and Figure 3-8.
Procedure
1) Orient the Bullet Nose-Type Fuseholder over its mounting position and firmly
press to seat the bullet-type connectors.
2) Remove the fuseholder portion from the mounted fuseholder body by pulling it
straight out. Install the TLS/TPS fuse into the fuseholder. When done, push the
fuseholder portion back into the mounted fuseholder body.
3) Ensure an alarm fuse is installed in the GMT-type fuseholder provided on the
mounted fuseholder body. The alarm fuse should be a Bussmann GMT 18/100
ampere alarm fuse. Emerson Network Power P/N 248610301.
4) Ensure a safety fuse cover is installed on the GMT alarm fuse. Emerson
Network Power P/N 248898700.
Installing Bullet Nose-Type Circuit Breakers
Refer to Figure 3-7 and Figure 3-8.
Procedure
1) Orient the circuit breaker over its mounting position with the ON position at top
and firmly press to seat the bullet-type connectors.
Installing an Optional Bullet Nose-Type 10-Position GMT Fuse Module
Refer to the procedure Installing and Wiring an Optional Bullet Nose-Type 10-Position
GMT Fuse Module in “Chapter 4. Making Electrical Connections”.
Storing Spare Fuses
Spare fuses may be stored in holders provided inside the bay, behind the MCA
Distribution Bus Monitoring circuit card hinged panels.
Recording Fuse and Circuit Breaker Sizes
Record all fuse and circuit breaker sizes installed on the cards provided on the MCA
Distribution Bus Monitoring circuit card hinged panels.