INSTALLING POWER/DISTRIBUTION BAY EXTERNAL TOP-
MOUNT VERTICAL BATTERY INPUT BUSBAR ASSEMBLY, P/N
554874 (IF FURNISHED)
Tools and Material Required to Install the Busbar Assembly
a) 9/16" Wrench (for 3/8" Hardware)
b) 15/16" Wrench (for 5/8" Hardware)
c) Channel Locks
d) Anti-Oxidation Compound
e) Torque Wrench
Installation Procedure
Danger: Before performing this procedure, ensure that the Power/Distribution Bay
is COMPLETELY DISCONNECTED from all power sources.
Note: Apply electrical anti-oxidation compound to mating surfaces of busbars before
connecting together.
Assemble the Busbar Kit to the top of the bays as shown in Figure 2-45 through Figure
2-52
.