Application Guide

Installation Instructions Section 5876
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AT, April 26, 2013
Chapter 2. Placing the Bays and Installing Internal/External Busbars Page 2-55
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 2-40
Power/Distribution Bay Load Return Lug Extension Busbar Assembly (P/N 514543)
Assembly Procedure Step 1B
(1*) Busbar, P
/N 514542
(8*) 3/8-16 x 3" Bolt,
P/N 227647800
(8*) 3/8" Flat Wa
sher, P/N 214204100
(hardene
d, thicker than other Kit
suppl
ied 3/8" flat washer)
(8*) 3/8
" Belleville Washer, P/N 21482
5000
(8*) 3/8-16 Nut, P/N 22856
7100
* Quantities are per Kit,
two Kits shown in Illustration
s.
Previously Assembled
Kit P
/N 514690 or 514691
Previously
Assembled
Kit P/N 554873
Note:
Concave Side of Belleville
Wa
sher Faces Busbar,
Convex Side
Faces Bolt Head.
Front Top
of B
ay
As
sembled
View
Torque to 180
in-lbs.
Note: Apply Electrica
l Anti-Oxidation
Compound to
all Busbar
Mating Surfaces.
STEP 1B
Install "Load Return Lug
Extension Busbar"
(List 2 and 1