Application Guide
Installation Instructions Section 5876
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AT, April 26, 2013
Chapter 2. Placing the Bays and Installing Internal/External Busbars Page 2-53
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 2-38
Power/Distribution Bay Load Return Lug Extension Busbar Assembly (P/N 514543)
Assembly Procedure Step 2A
STEP 2A
Install "Lug Mounting Bolts"
(List 1 and 11 Bays).
(24*) 3/8-16 x 1-1/4" Bolt, P/N 227646800
(24*) 3/8" Flat Washer, P/N 214112100
(thinner than other Kit
supplied 3/8" flat washer)
(24*) 3/8" Flat Washer, P/N 214112100
(thinner than other Kit
supplied 3/8" flat washer)
(24*) 3/8" Lock Washer, P/N 215111300
(24*) 3/8-16 Nut, P/N 228567100
Previously Assembled
Kit P/N 514688 or 514689
Previously Assembled
Kit P/N 554873
Torque to 300 in-lbs.
* Quantities are per Kit
,
two Kits shown in Illustrations.
Front Top
of Bay
Assembled
View
PROCEDURE PROVIDED FOR REFERENCE ONLY,
INSTALL BOLTS AS LUGS ARE INSTALLED TO BUSBAR