Application Guide
Installation Instructions Section 5876
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AT, April 26, 2013
Chapter 2. Placing the Bays and Installing Internal/External Busbars Page 2-51
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
INSTALLING POWER/DISTRIBUTION BAY LOAD RETURN LUG
EXTENSION BUSBAR ASSEMBLY, P/N 514543 (IF FURNISHED)
Tools and Material Required to Install the Busbar Assembly
a) 9/16" Wrench (for 3/8" Hardware)
b) Cross-Blade Screwdriver
c) Anti-Oxidation Compound
d) Torque Wrench
Installation Procedure
Danger: Before performing this procedure, ensure that the Power/Distribution Bay
is COMPLETELY DISCONNECTED from all power sources.
Note: Apply electrical anti-oxidation compound to mating surfaces of busbars before
connecting together.
Assemble the Busbar Kit to the top of the bays as shown in Figure 2-37 through Figure
2-42. Refer to Figure 2-43 and Figure 2-44
for assembled views. Note that this Busbar
Kit requires "External Top-Mount Ground (Load Return) Busbar Assembly" P/N 514688,
514689, 514690, or 514691. This Busbar Kit attaches to the P/N 514688, 514689,
514690, and 514691 Busbar Kits.