Application Guide

Section 5876 Installation Instructions
Issue AT, April 26, 2013 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 2-28 Chapter 2. Placing the Bays and Installing Internal/External Busbars
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 2-16
Power/Distribution Bay External Top-Mount Horizontal Busbar Assembly (P/N 554873)
Assembly Procedure Step 3
Assembled
View
STEP 3
Install “Main Negative Busbar” onto Bay’s
Negative Busbar. Hand-tighten hardware.
(1) Main Negative Busbar, P/N 554875
Rear Top
of Bay
Note: Apply Electrical Anti-Oxidation Compound
to Busbar Mating Surfaces.
(8) 3/8” Flat Washer, P/N 214204100
(8) 3/8” Belleville Washer, P/N 214825000
(8) 3/8-16 Hex Nut, P/N 228567100 Hand-Tighten
Note: Concave Side of Belleville Washer Faces
Busbar, Convex Side Faces Hex Nut.
Belleville Washer Install between Hext Nut
and Flat Washer.
Mount 554876 to the 554875.
Hardware:
214204100 (4)
214825000 (4)
228567100 (4)