Application Guide
Installation Instructions Section 5876
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AT, April 26, 2013
Chapter 5. Installing the Rectifiers and Initially Starting the System Page 5-39
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
c) Requirement: FA indicator off.
(located inside bay, center section)
d) Requirement: Status indicator located on the following circuit cards green.
MCA/Router circuit card
LMS CPU circuit card (if installed)
MCA Customer Alarm Relay circuit card (if installed)
Distribution Only Bay:
a) Requirement: BAY ALARM indicator green.
(located on outside of door at top)
b) Requirement: Distribution Bus indicator green.
(located on hinged panel covering
MCA Distribution Bus Monitoring circuit cards)
c) Requirement: POWER indicator green.
(located inside bay, top section)
d) Requirement: FA indicator off.
(located inside bay, top section)
e) Requirement: Status indicator located on the following circuit cards green.
Router circuit card
MCA Distribution Bus Monitoring circuit cards
Checking and Configuring the LMS System
Refer to the separate LMS Installation Instructions (Section 5879). Section 5879 can be
accessed from the CD (Electronic Documentation Package) furnished with your system.