Application Guide

Installation Instructions Section 5876
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AT, April 26, 2013
Chapter 5. Installing the Rectifiers and Initially Starting the System Page 5-37
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
displayed. When all Distribution Devices are cycled through, GO TO
DISTRIBUTION LOAD MENU is displayed.
10) With GO TO DISTRIBUTION LOAD MENU being displayed, press and release
the FUNCTION SET ENTER key.
11) Repeatedly press and release the FUNCTION SELECT DOWN arrow key and
FUNCTION SET ENTER key to display the load currents through the remaining
Distribution Panels and Distribution Devices.
12) Navigate to the DISTRIBUTION LOAD MENU.
13) Repeatedly press and release the FUNCTION SELECT DOWN arrow key to
display individual load currents of any MCA I/O circuit card set as
DISTRIBUTION.
14) When done, navigate to GO TO MEASUREMENT MENU in the DISTRIBUTION
LOAD MENU.
15) With GO TO MEASUREMENT MENU being displayed, press and release the
FUNCTION SET ENTER key.
16) Press and release the FUNCTION SELECT DOWN arrow key.
a) Requirement: Distribution Group A load current is displayed.
17) Press and release the FUNCTION SELECT DOWN arrow key.
a) Requirement: Distribution Group B load current is displayed.
18) Press and release the FUNCTION SELECT DOWN arrow key.
a) Requirement: Total auxiliary load current is displayed.
19) Press and release the FUNCTION SET ENTER key.
a) Requirement: The load current of the first MCA I/O circuit card set as
AUXILIARY is displayed.
20) Repeatedly press and release the FUNCTION SELECT DOWN arrow key to
display individual load currents of any MCA I/O circuit card set as AUXILIARY.
21) When done, navigate to GO TO MEASUREMENT MENU in the DISTRIBUTION
LOAD MENU.
22) With GO TO MEASUREMENT MENU being displayed, press and release the
FUNCTION SET ENTER key.
23) Press and release the FUNCTION SELECT DOWN arrow key.
a) Requirement: Total Rectifier output current is displayed.
Please Note: Due to small differences in calibration between Rectifiers
and the Distribution Shunts, this value may not be equal to that seen in
Step 6).
24) Press and release the FUNCTION SET ENTER key.
a) Requirement: Output current of the first Rectifier is displayed.
25) Repeatedly press and release the FUNCTION SELECT DOWN arrow key to
display individual output currents of the remaining Rectifiers.
a) Requirement: As the FUNCTION SELECT DOWN arrow key is pressed
and released, output currents of the remaining Rectifiers are displayed.
When all Rectifiers are cycled through, GO TO MEASUREMENT MENU is
displayed.