Application Guide

Installation Instructions Section 5876
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AT, April 26, 2013
Chapter 5. Installing the Rectifiers and Initially Starting the System Page 5-19
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Note: There is a 20 second timeout. If the MCA times out, press ALARM
CUTOFF and FUNCTION SET ENTER again.
6) Press and hold the FUNCTION SET YES (+) or NO (-) key to set the number of
PCU (Rectifier) positions available in the system (empty and filled). Release the
key when the desired value is displayed.
7) With the desired value being displayed, press and release the FUNCTION SET
ENTER key.
8) “ARE YOU SURE?” is displayed. Press and release the FUNCTION SET YES
(+) key.
9) Scroll up and down through the remaining Inventory Items using the FUNCTION
SELECT UP and DOWN arrow keys. Verify that the Inventory Items are correct
for your system.
10) When done, press and release the FUNCTION SET YES (+) and NO (-) keys
simultaneously, to return to the beginning of the MCA menu tree.
Setting the Date and Time
Procedure
1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key.
2) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
CHANGE CONFIGURATION PARAMETERS is displayed.
3) Press and release the FUNCTION SET ENTER key.
4) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until IT
IS NOW hh.mm.ss dd-mon-yy is displayed.
5) Press and release the ALARM CUTOFF and FUNCTION SET ENTER keys
simultaneously. The day of the month is underlined.
6) Press FUNCTION SET YES (+) and NO (-) keys to change the day of month.
7) Press FUNCTION SET ENTER key. Month is underlined.
8) Press FUNCTION SET YES (+) and NO (-) keys to change the month.
9) Press FUNCTION SET ENTER key. Year is underlined.
10) Press FUNCTION SET YES (+) and NO (-) keys to change the year.
11) Press FUNCTION SET ENTER key. Hour is underlined.
12) Press FUNCTION SET YES (+) and NO (-) keys to change the hour.
13) Press FUNCTION SET ENTER key. Minutes is underlined.
14) Press FUNCTION SET YES (+) and NO (-) keys to change the minutes.
15) Press FUNCTION SET ENTER key.
Setting the Temperature Units (degrees C or degrees F)
Procedure
1) With SYSTEM OK being displayed on the MCA Interface Pad, press and release
the FUNCTION SET ENTER key.
2) Repeatedly press and release the FUNCTION SELECT DOWN arrow key until
CHANGE CONFIGURATION PARAMETERS is displayed.