Application Guide
Installation Instructions Section 5876
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AT, April 26, 2013
Chapter 5. Installing the Rectifiers and Initially Starting the System Page 5-17
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
PCU SEQUENCING IS
DISABLED
or
PCU SEQUENCING DELAY
= ss SECONDS
Allows you to enable the Rectifier
Sequencing feature and set the
Rectifier Sequencing Delay set
point, or disable the feature.
Note: To disable the feature, press
NO / - when in the change setting
mode to scroll to Rectifier
SEQUENCING IS DISABLED
(displayed when you scroll down to
"zero seconds").
TEST EQUALIZE IS DISABLED
TURN OFF POWER SHARE
or
MANUAL TEST/EQUALIZE
= hh HOURS
or
TEST/EQUALIZE STOP
IS MANUAL
Allows you to enable the Manual
Timed Test/Equalize feature and set
the Timed Test/Equalize set point,
or disable the feature.
Note: To disable the feature, press
NO / - when in the change setting
mode to scroll to TEST/EQUALIZE
STOP IS MANUAL (displayed when
you scroll down to "zero hours").
This indicates the manually initiated
timed test/equalize feature is
disabled and the system must be
manually returned to the float mode
if placed in the test/equalize mode.
When the Power Share feature is
enabled, the system cannot be
placed in the Test/Equalize mode.
Note: Test/Equalize Mode requires
Power Share to be turned off. A
message is displayed if Power
Share is on.
AUTO EQUALIZE IS
DISABLED
or
TURN OFF POWER SHARE
or
AUTO EQUALIZE FOR ##
x DISCHARGE
Allows you to enable the Auto
Test/Equalize feature and set the
Auto Test/Equalize Multiplier set
point, or disable the feature.
Note: To disable the feature, press
NO / - when in the change setting
mode to scroll to AUTO EQUALIZE
IS DISABLED (displayed when you
scroll down to "zero x discharge").
When the Power Share feature is
enabled, the system cannot be
placed in the Test/Equalize mode.
Note: Test/Equalize Mode requires
Power Share to be turned off. A
message is displayed if Power
Share is on.