Application Guide
Installation Instructions Section 5876
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AT, April 26, 2013
Chapter 5. Installing the Rectifiers and Initially Starting the System Page 5-15
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
the new value, or the FUNCTION SET NO (-) key to cancel this operation without
changing the setting. Display the next or previous entry using the FUNCTION
SELECT UP or DOWN arrow key. Repeat this procedure for each entry
presented.
When all the adjustable values have been properly set, press the FUNCTION
SELECT DOWN arrow key until READY TO START THE SYSTEM NOW? is
displayed. Press and release the ALARM CUTOFF and FUNCTION SET
ENTER keys simultaneously. At the "ARE YOU SURE?" prompt, press the
FUNCTION SET YES (+) key. The MCA starts the system.
FLOAT SETPOINT
= vv.vvV
Allows you to change the Float
Output Voltage set point.
TEST/EQUALIZE
= vv.vvV
Allows you to change the
Test/Equalize Output Voltage set
point.
HI VOLTAGE SHUTDOWN
= vv.vvV
Allows you to change the High
Voltage Shutdown set point.
PCU CURRENT LIMIT
= aaaaaA
or
PCU CURRENT LIMIT
= aaaaaMAX
or
PCU CURRENT LIMIT
POWER SHARE
or
PCU CURRENT LIMIT
ALT. LIMIT
Allows you to change the Current
Limit set point. aaaaaA = System
current limit setting, current limit
circuit on all Rectifiers are
automatically adjusted to ensure
system current does not exceed this
value. aaaaaMAX = System current
limit setting is set to the sum of the
maximum current capacities of all
Rectifier Modules installed in the
system.
Note: When Power Share is
enabled, current limit is controlled
by the Power Share feature.
Note: When Alternate Current Limit
is enabled and active, current limit
is controlled by the Alternate
Current Limit feature.
SYSTEM HI VOLTAGE #1
= vv.vvV
Allows you to change the System
High Voltage #1 Alarm set point.
SYSTEM HI VOLTAGE #2
= vv.vvV
Allows you to change the System
High Voltage #2 Alarm set point.
BATTERY ON DISCHARGE
= vv.vvV
Allows you to change the Battery on
Discharge Alarm set point.
VERY LOW VOLTAGE
= vv.vvV
Allows you to change the Very Low
Voltage Alarm set point.
TOTAL DISTRIBUTION
= aaaaaA
Allows you to change the Total
Distribution Load Current Alarm set
point.
DISTRIBUTION GROUP A
= aaaaaA
Allows you to change the
Distribution Group A Load Current
Alarm set point.