Application Guide
Section 5876 Installation Instructions
Issue AT, April 26, 2013 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 5-2 Chapter 5. Installing the Rectifiers and Initially Starting the System
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
INSTALLING THE RECTIFIERS
Install Rectifiers from top to bottom, starting with the top most mounting position. (In the
MCA display messages, the Rectifiers are designated per bay and are numbered from 1
to 10, starting with the top most position. See the Navigating the MCA chapter in the
USER INSTRUCTIONS, Section 5877.)
The Rectifier weighs approximately 40 lbs.
Rectifiers can be inserted or removed with power applied (hot swappable).
Procedure
1) Remove the blank panel from the Rectifier mounting position. Save this panel.
The panel must be re-installed if a Rectifier is removed.
Note: In the next step, a safety latch is present on the left-hand (as viewed from the
front) side panel of each Rectifier. The latch is designed to prevent the
Rectifier from inadvertently being removed completely from the bay once it
has been installed. It should not be necessary to depress the safety latch
release when installing the Rectifier.
2) Install the Rectifier into the bay by sliding it evenly into its mounting position.
Secure the Rectifier to the bay by tightening the captive fasteners on the
Rectifier.
3) Perform steps 1) and 2) for each Rectifier to be installed.