Application Guide

Section 5876 Installation Instructions
Issue AT, April 26, 2013 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 2-4 Chapter 2. Placing the Bays and Installing Internal/External Busbars
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Note: A ground washer is an internal-external tooth, dish-type lock washer.
When installing ground washers, ensure that the ground washer is
oriented so that the teeth dig into the paint on the metal part the ground
washer is secured to (concave side faces the metal part).
4) Install shims between bottom of each bay and the floor as required to distribute
floor loading.
5) Secure bay(s) to floor using fastening hardware per site requirements.
1) If the outside sides of the end bays do not have side cover panels, install them
now (two per side). Note that ground washers are used with each screw
securing the side cover panels.
Installing Side Cover Panels on End Bays
a) Install the rear-most side cover panel as follows: Insert tabs at front of
cover panel into slots in bay. Pivot cover panel into position against side of
bay. Install the previously removed screws and ground washers into cover
panel from rear of bay.
b) Install the front-most side cover panel as follows: Open the bay's front
door. Insert tabs at rear of cover panel into slots in bay. Pivot cover panel
into position against side of bay. Install the previously removed screws and
ground washers into cover panel from front of bay.