Application Guide

Installation Instructions Section 5876
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AT, April 26, 2013
Chapter 4. Making Electrical Connections Page 4-73
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Connecting a 582140000 Main Power Bay to a
Legacy Power System (LMS Interconnections)
See Figure 4-30.
Interface Notes
1) Connect shunt leads from the Legacy System to an LMS analog card installed in the
582140000 System.
2) Connect RFA leads from the Legacy System to an LMS binary card installed in the
582140000 System.
3) Connect FA leads from the Legacy System to an LMS binary card installed in the
582140000 System.
4) For each legacy rectifier, program an LMS Energy Management Channel using the
associated inputs. Program the LMS for Energy Management. Refer to the LMS
User document.
5) If the Legacy System requires sequencing of rectifiers, program the LMS sequencing
option. Sequencing also requires an LMS Relay Card(s) (58650550040) to be
installed in the 582140000 system and connected to the legacy rectifiers. Refer to
the LMS User document.
6) Update the LMS Function Channel 0063 program line to sum the analog inputs used
in Step 1) for distribution shunts.
7) Update the LMS Function Channel 0064 program line to sum the analog inputs used
in Step 1) for rectifier shunts.
8) Update the LMS LED Channel 0007 program line to include the binary inputs used in
Step 3).