Application Guide
Installation Instructions Section 5876
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AT, April 26, 2013
Chapter 4. Making Electrical Connections Page 4-61
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
RE-INSTALL SHIELDS AND COVER PANELS
1) Replace all shields and cover panels that were removed when performing the
procedures in Chapter 2. Refer to Chapter 2 for illustrations. Specifically…
• Replace front Rectifier mounting position blank cover panels (only for mounting
positions NOT to be populated with Rectifiers). To do so: Secure the cover
panel with the two screws removed earlier. Use the supplied grounding washers
at both locations, per cover panel.
• Replace the three rear cover panels to each Power/Distribution and Power Only
Bay. To do so:
Lower Panels: Secure the cover panels with the screws
removed earlier. Use the supplied grounding washers at all locations.
Top
Panel:
• Replace the two rear cover panels to each Distribution Only Bay.
Place the keyhole slots in the cover panel over the screws in the bays,
slide the cover panel down and secure by tightening the screws.
• Ensure side cover panels are installed on end bays, as described in Chapter 2.
• Lists 2 and 12 only: Replace the front cover panel to each PDSC. To do so:
Secure the cover panel with the eight screws removed earlier. Use the supplied
grounding washers at the top left and bottom right locations.
• Lists 2 and 12 only: Replace the rear lower cover panel to each PDSC. To do
so: Secure the cover panel with the six screws removed earlier. Use the
supplied grounding washers at the top left and bottom right locations.
• Lists 2 and 12 only: Replace the rear upper cover panel to each PDSC. To do
so: Place the keyhole slots in the cover panels over the screws in the PDSCs,
slide the cover panels down and secure by tightening the screws. Use the
supplied grounding washers at the top left and bottom right locations.
2) For bays with PDSCs, install the bay-to-bay busbar link cover shield.