Application Guide
Section 5876 Installation Instructions
Issue AT, April 26, 2013 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 4-58 Chapter 4. Making Electrical Connections
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-22
Battery Connection to Optional Horizontal Battery Termination Assembly on Power/Distribution Bays
Figure 4-23
Battery Connection to Optional Vertical Battery Termination Assembly on Power/Distribution Bays
POSITIVE BATTERY
(GROUND RETURN +48V)
NEGATIVE BATTERY
(SUPPLY -48V)
Top Rear
of Bay
Recm. Torque
3/8" Hardware
using Belleville
Lock Washer
180 in-lbs, using
flat washer and
lock washer
300 in-lbs.
Top Rear
of Bay
POSITIVE BATTERY
(GROUND RETURN +48V)
NEGATIVE BATTERY
(SUPPLY –48V)
Recm. Torque
3/8” Hardware:
Using Bellevile Washer
180 in-lbs.
Using Flat Washer & Lock Washer
300 in-lbs