Application Guide

Installation Instructions Section 5876
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AT, April 26, 2013
Chapter 4. Making Electrical Connections Page 4-45
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Figure 4-15
AC Input and AC Input Ground Connections
(Lists 1 and 11 Bays, w/out PDSC)
PCU #1
PCU #2
PCU #3
PCU #4
PCU #5
PCU #6
PCU #7
PCU #9
PCU #10
Front View
PCU #1
A B C
PCU #2
A B C
PCU #3
A B C
PCU #7
A B C
PCU #8
A B C
PCU #9
A B C
PCU #10
A B C
PCU #6
A B C
PCU #5
A B C
PCU #4
A B C
480VAC (List A) or 208VAC (List B), 3 Phase, 60Hz
Separate Feed per PCU
PCU AC INPUT: 1/4-20 Studs on 5/8" Centers for Installation of Customer Provided Two-Hole Lugs
Frame Ground
(1/4-20 Studs
for Installation of
Customer Provided
One-Hole Lugs)
Recm. Torque
Using supplied
1/4" hardware,
84 in-lbs.
Cover Removed
in Illustration