AC INPUT AND AC INPUT GROUND CONNECTIONS
Note: Refer to System Application Guide SAG582140000 for recommended wire size,
branch circuit protection, and crimp lugs. Refer also to the SAG for maximum size
of wire to connect to the various lug landing points. Refer to drawing 031110100
for lug crimping information. Refer to drawings 031110200 and 031110300 for
additional lug information. The SAG and Engineering Drawings can be accessed
via the CD (Electronic Documentation Package) furnished with your system.
• PDSC = AC Input 'Power Distribution Service Cabinet'.
Wiring Routing Guidelines
Lists 1 and 11 Bays (w/out PDSC): Ten circular openings are provided in the top of
each bay for AC input and AC input grounding conductors. Conduit adapter plates are
also furnished. These adapter plates accept 3/4" or 1" inch conduit fittings. Conduit
fittings should be installed, and AC input and AC input grounding conductors should be
routed into the cabinet through these openings.
Lists 2 and 12 Bays (with PDSC): Three wiring access plates are secured to the top of
the PDSC to provide a choice of wiring access openings. Choose one of the plates, and
remove the two not needed. Conduit fittings should be installed, and AC input and AC
input grounding conductors should be routed into the cabinet through these openings.
Lists 3 and 13 Bays: Six circular openings are provided in the top of each bay for AC
input and AC input grounding conductors. Conduit adapter plates are also furnished.
These adapter plates accept 1.75" inch conduit fittings. Conduit fittings should be
installed, and AC input and AC input grounding conductors should be routed into the
cabinet through these openings.
Lists 4 and 14 Bays: Two circular openings are provided in the top of each bay for AC
input and AC input grounding conductors. Conduit adapter plates are also furnished.
These adapter plates accept 1" inch conduit fittings. Conduit fittings should be installed,
and AC input and AC input grounding conductors should be routed into the cabinet
through these openings.
Lists 5 and 15 Bays: Ten circular openings are provided in the top of each bay for AC
input and AC input grounding conductors. Conduit adapter plates are also furnished.
These adapter plates accept 3/4" or 1" inch conduit fittings. Conduit fittings should be
installed, and AC input and AC input grounding conductors should be routed into the
cabinet through these openings.