Application Guide
Section 5876 Installation Instructions
Issue AT, April 26, 2013 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 4-18 Chapter 4. Making Electrical Connections
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
MCA Relay
Function
Channel #
Alarm
Name
Alarm
Configuration
Assigned to
Relay #…
installed in
Slot #…
of any Bay
7 Very Low Voltage Alarm System Voltage is Very Low 1 6 and 2
8 High Voltage Alarm #2
System High Voltage
#2 Alarm
2 6 and 2
9 Audible Alarm Contacts
See Relay Function
Channel 25
3 6 and 2
10 Test / Equalize Indication Test/Equalize Mode is Active 4 6 and 2
11 Rectifier Fail Alarm
1 PCU Failure Any Type, 2+
PCU Failures Any Type, No
PCU in Inventory (installed)
5 6 and 2
12 Rectifier Major Alarm
2+ PCU Failures 'Major'
Type, No PCU in Inventory
(installed)
6 6 and 2
13 Rectifier Minor Alarm
1 PCU Failure 'Minor' Type,
2+ PCU Failures 'Minor'
Type, 1 PCU Failure 'Major'
Type
1 5 and 1
14 Over Current Alarm
Total Distribution Load Alarm,
Distribution Group A Load
Alarm, Distribution Group B
Load Alarm
2 5 and 1
15 AC Major Alarm
AC Power is Off to All PCUs,
AC Power is Off to 2+ PCUs
3 5 and 1
16 AC Minor Alarm AC Power is Off to 1 PCU 4 5 and 1
17 MCA Fail Alarm
Controller (MCA) Failure,
Controller Initializing
5 5 and 1
18 Undefined -- 6 5 and 1
19 Undefined -- 1 4
20 Undefined -- 2 4
21 Undefined -- 3 4
22 Undefined -- 4 4
23 Undefined -- 5 4
Table 4-1A (cont'd from previous page, cont'd on next page)
Default MCA Relay Function Channel Configurations and
Default MCA Customer Alarm Relay Assignments