Application Guide
Section 5957 Installation Guide
Issue AM, March 26, 2014 Spec. No. 582140000 (Models 802NLDB, 802NLEB and 802NL-B)
Page 92
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Setting Switch S1 on the MCA Circuit Card in the Primary Power/Distribution and Power Only Bay
The individual switches of S1 have the following functions.
Note that the switch ON position is the UP position.
Switch of S1
Designation
Function
1
MCA
When in the ON position,
the MCA section of the
circuit card is disabled.
2
MON
When in the ON position,
changing Power System
settings via LMS is disabled.
3
KEY
When in the ON position,
changing Power System
settings via MCA Keypad is
disabled.
4
PRO
When in the ON position,
the remote uploading of new
firmware into the circuit card
is forced. This switch is used
for diagnostic purposes only.
MCA CIRCUIT CARD
(P/N 509478)
(PRIMARY BAY)
S1
1 2 3 4
ON = UP
J4
MCA DISTRIBUTION BUS MONITORING CIRCUIT CARD (P/N 524982)