LMS Local Port
Introduction
The LMS Local Port is provided via a USB to RS-232 Port Adapter Unit. The proper
device driver must be installed on the computer to be connected to the USB port. Use
one of the following procedures to install the device driver.
Installing the USB Device Driver from the Furnished CD
A device driver CD is supplied with the USB to RS-232 Port Adapter Unit. The proper
driver must be installed on the computer to be connected to the USB port. Use the
provided CD to install the driver.
Downloading the USB Driver from the Web
1) Go to this link http://vscom.de/downloadcenter.htm.
2) Select “USB to Serial Drivers” from the Product Category drop-down menu.
3) Select your product model’s “Driver and Documentation” to download the files.
4) Select your computer’s operating system.
5) Run or save the application.
Setting up your Computer to Access the Power System
1) Select Hyper terminal.
2) Connect using one of the unused COM ports. (e.g. COM 5)
3) Set Bit Per Second to 19200.
4) Set Data Bits to 8.
5) Set Parity to None.
6) Set Stop bits to 1.
7) Set Flow control to Hardware.
8) Select OK.
9) In Hyper terminal press ENTER.
10) Enter the password 6.
11) Enter “?” to see commands.