Application Guide

System Application Guide SAG582140000
Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B) Issue AW, June 3, 2014
Page 99 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
SPECIFICATIONS
1. SYSTEM
1.1 DC Operating Voltage
1.1.1 Nominal: -48Vdc.
1.1.2 Range: -42Vdc to -60Vdc.
1.2 Environmental Ratings
Note: See also ‘Environmental Ratings’ in the Rectifier Module section.
1.2.1 Operating Ambient Temperature Range: C to +40°C (+32°F to +104°F).
1.2.2 Storage Ambient Temperature Range: -40°C to +65°C (-40°F to +149°F).
1.2.3 Humidity: This system is capable of operating in an ambient relative humidity range of 0% to
95%, noncondensing.
1.2.4 Altitude: The maximum operating ambient temperature should be derated by 10°C at an
elevation of 10,000 feet above sea level. For elevations between 3,000 feet and 10,000 feet,
derate the maximum operating ambient temperature linearly.
1.2.5 Heat Dissipation: With R48-11600 Rectifier(s) output adjusted to 54.48 volt DC at rated full
load and nominal input voltage.
R48-11600 Rectifier (P/N 486532602)
No. of
Rectifiers
Bay Output Current
(Amperes)
BTU/Hr
(Typical)
1
0 (Rectifier no load)
1
1
100 (Rectifier half load)
1552
1
200 (Rectifier full load)
3108
2
400
6216
3
600
9324
4
800
12432
5
1000
15540
6
1200
18648
7
1400
21756
8
1600
24864
9
1800
27972
10
2000
31080