Application Guide

SAG582140000 System Application Guide
Issue AW, June 3, 2014 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 92 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Power Only Bay AC Input, Two (2) AC Feeds
Wire Sizes, Branch Circuit Protection, and Lugs
Features
Studs (3/8-16 on 1" centers) are provided for installation of customer provided two-hole AC Input lugs and
frame ground lugs.
For lug mounting hole size and spacing dimensions, refer to the illustration provided in this section.
Restrictions
All lugs for customer connections must be ordered separately.
List 4 and 14 provides two (2) AC feeds.
Ordering Notes
1) Refer to Table 18 for recommended wire sizes, branch circuit protection, and lugs.
AC Feeds #1 and #2
Ambient
Operating
Temperature
(1)
Nominal
Input
Voltage
(VAC)
Recm
Branch
Circuit
Protection
(Amperes)
(2)
Line Ground
(5)
Recm 75
°
C
Wire Size
(AWG)
(1)
Recommended
Crimp Lug
(3)
Recm 75
°
C
Wire Size
(AWG)
(4)
Recommended
Crimp Lug
(3)
40°C
480
100
(6)
2
245348200
2
245348200
240
200
3/0
245347300
3/0
245347300
208
225
4/0
245347400
4/0
245347400
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper
wire at 75°C conductor temperature, operating in an ambient of 40
°C was used. For other operating
ambient temperatures, refer to the National Electrical Code. For operation in countries where the NEC is
not recognized, follow applicable codes.
2
The AC input branch circuit protective device should be of the time-delay or high inrush type.
3
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug crimping
information.
4
Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper
wire. If aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for
increased conductor size. For operation in countries where the NEC is not recognized, follow applicable
codes.
5
Equipment grounding conductors must be provided with the AC input conductors supplied to the Bay.
Frame ground terminals must be connected to earth ground, not power system neutral.
6
Maximum overcurrent protection device is 110A.
Table 18
Recommended AC Input Wire Size and Lug Selection
Two (2) AC Feeds
Home