Application Guide
SAG582140000 System Application Guide
Issue AW, June 3, 2014 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 88 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Power/Distribution Bay AC Input, One (1) AC Feed
Wire Sizes, Branch Circuit Protection, and Lugs
Features
♦ Studs (3/8-16 on 1" centers) are provided for installation of customer provided two-hole AC Input lugs.
These studs are accessed from the rear of the PDSC (AC Input 'Power Distribution Service Cabinet').
♦ Captive nuts (3/8-16 on 1" centers) are provided for installation of customer provided frame ground lugs.
These studs are accessed from the rear of the PDSC (AC Input 'Power Distribution Service Cabinet').
♦ For lug mounting hole size and spacing dimensions, refer to the illustration provided in this section.
Restrictions
All lugs for customer connections must be ordered separately.
Requires optional bolt-on PDSC (AC Input 'Power Distribution Service Cabinet') (List 30 or 31).
For use with List 2 and 12 only.
Ordering Notes
1) Refer to Table 16 for recommended wire sizes, branch circuit protection, and lugs.
AC Feed #1
Ambient
Operating
Temperature
(1)
Nominal
Input
Voltage
(VAC)
Recm
Branch
Circuit
Protection
(Amperes)
(2)
Line Ground
(5)
Recm 90
°
C
Wire Size
(AWG and
kcmil)
(1)
Recommended
Crimp Lug
(3)
Recm 90
°
C
Wire Size
(AWG and
kcmil)
(4)
Recommended
Crimp Lugs
(3)
30°C
and
40°C
480 200 3/0 245347300 3/0 245347300
208 500 750 245348100 750 245348100
1
Wire sizes based on recommendations of the American National Standards Institute (ANSI) approved
National Fire Protection Association's (NFPA) National Electrical Code (NEC). Table 310-16 for copper
wire at 90°C conductor temperature, operating in ambients of 30
°C and 40°C was used. For other
operating ambient temperatures, refer to the National Electrical Code. For operation in countries where
the NEC is not recognized, follow applicable codes.
2
The AC input branch circuit protective device should be of the time-delay or high inrush type.
3
Two-hole lug, 3/8" bolt clearance hole, 1" centers. Refer to drawing 031110100 for lug crimping
information.
4
Equipment grounding conductor size based on recommendations of the NEC Table 250-122 for copper
wire. If aluminum or copper clad aluminum grounding conductor is used, refer to Table 250-122 for
increased conductor size. For operation in countries where the NEC is not recognized, follow
applicable codes.
5
Equipment grounding conductors must be provided with the AC input conductors supplied to the Bay.
Frame ground terminals must be connected to earth ground, not power system neutral.
Table 16
Recommended AC Input Wire Size and Lug Selection
One (1) AC Feed
Home