Application Guide
SAG582140000 System Application Guide
Issue AW, June 3, 2014 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 74 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Power/Distribution Bay and Distribution Only Bay Load Distribution Wire Sizes and Lugs
Features
♦ Load distribution leads are connected as described in the sections titled Distribution Devices and Load
Lug Locations - Power/Distribution Bays and Distribution Device and Load Lug Locations – Distribution
Only Bays under "Accessory Descriptions". For lug mounting hole size and spacing dimensions, refer to
the illustrations in these sections.
Restrictions
All lugs for customer connections must be ordered separately.
Ordering Notes
1) The type of distribution device determines the load lug hole size and spacing requirements. The rating of
the distribution device determines the wire size requirements. For wire size and lug selection; refer to
Tables 9 and 10 (Load Side). Load return leads for Power/Distribution Bays are terminated either inside
the bay if equipped with the optional internal ground busbar, or outside the bay if equipped with the
optional external ground busbar mounted on top of the bay. Load return leads for distribution only bays
are terminated outside the bay to customer provided return busbars.
2) For other available lugs and hardware, refer to drawings 031110100 through 031110300.