Application Guide

SAG582140000 System Application Guide
Issue AW, June 3, 2014 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 72 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Wiring Components
Power/Distribution and Power Only Bays Frame Grounding Wire Sizes and Lugs
Features
Two sets of captive nuts (1/4-20 on 5/8" centers) are provided for installation of customer provided two-
hole lugs.
For lug mounting hole size and spacing dimensions, refer to the illustration provided in this section.
Restrictions
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting bolts and hardware.
The recommended frame ground wire size is 6 AWG.
Recommended lug P/N 245346700.
Two holes with 1/4-20 captive
nuts provided for installation of
customer provided two-hole lug
with 1/4" bolt clearance holes
on 5/8" centers
Two holes with 1/4-20 captive
nuts provided for installation of
customer provided two-hole lug
with 1/4" bolt clearance holes
on 5/8" centers
Top View
Power/Distribution Bays
(Power Only Bays Similar)
Home