Power/Distribution and Power Only Bays External Busbars
Optional External Top-Mount Horizontal Battery Input Busbar Assembly
Features
♦ Provides a battery input busbar assembly which mounts to the top of the bay.
♦ Provides horizontal lug landings for installation of customer provided two-hole lugs with 3/8" clearance
holes on 1" centers.
Restrictions
Rated for 2000 amperes.
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting bolts and hardware.
Not available when optional P/N 554874 External Top-Mount Vertical Battery Input Busbar Assembly is
installed. Bay will accept one or the other; not both.
Ordering Notes
1) Order an External Top-Mount Horizontal Battery Input Busbar Assembly per bay as required, P/N
554873.
Optional Busbar Shield Kit
Features
♦ Provides a plastic shield which mounts below the "Negative Battery (Supply -48V)" busbar on the External
Top-Mount Battery Input Busbar Assembly P/N 554873.
Restrictions
Requires the External Top-Mount Battery Input Busbar Assembly P/N 554873.
Ordering Notes
1) Order a Busbar Shield Kit (P/N 528482) as required for each External Top-Mount Battery Input Busbar
Assembly ordered.
Optional External Top-Mount Ground (Load Return) Busbar Assemblies
Features
♦ Provides a ground busbar assembly which mounts to the External Top-Mount Battery Input Busbar
Assembly P/N 554873.
♦ Provides for installation of customer provided two-hole lugs with 3/8" clearance holes on 1" centers.
Restrictions
Requires the External Top-Mount Battery Input Busbar Assembly P/N 554873.
All lugs for customer connections must be ordered separately.
Customer needs to supply lug mounting bolts and hardware.
Ordering Notes
1) Order an External Top-Mount Ground (Load Return) Busbar Assembly per bay as required.
P/N 514688, 6000A, for use with List 1 and 11 (no PDSC [AC Input 'Power Distribution Service Cabinet'])
or List 3, 4, 5, 13, 14, and 15.
P/N 514689, 10000A, for use with List 1 and 11 (no PDSC [AC Input 'Power Distribution Service
Cabinet']) or List 3, 4, 5, 13, 14, and 15.
P/N 514690, 6000A, for use with List 2 and 12 equipped with a List 30 or 31 PDSC (AC Input 'Power
Distribution Service Cabinet').
P/N 514691, 10000A, for use with List 2 and 12 equipped with a List 30 or 31 PDSC (AC Input 'Power
Distribution Service Cabinet').