Application Guide

SAG582140000 System Application Guide
Issue AW, June 3, 2014 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 54 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Optional Bullet Nose-Type 10-Position GMT Fuse Module for List C
Features
Installs in the optional List C Fuse/Circuit Breaker Panel.
Provides 10 GMT fuse positions.
(1/4A to 15A GMT Alarm-Type Fuses).
Screw clamp type load and load return terminals provided.
Includes ten dummy fuses equipped with safety fuse covers.
Includes 35A input fuse and associate alarm fuse.
Restrictions
30A maximum capacity per block.
Terminal block wire size capacity: 24 to 14 AWG.
Requires five (5) bullet device mounting positions.
When used for power distribution, load should not exceed 80% of device
rating, except 10 and 15 Amp fuses, for which load should not exceed 70%
of device rating.
Ordering Notes
1) Order optional Bullet Nose-Type 10-Position GMT Fuse Module (P/N 509128)
as required.
2) Order GMT fuses as required per Table 6.
3) See “Replacement Alarm, Reference, and Control Fuses” and Table 8 for ordering replacement input fuse
and associated alarm fuse.
Ampere Rating Part Number Fuse Color
18/100 GMT-A 248610301 ---
1/4 248610200 VIOLET
1/2 248610300 RED
3/4 248610500 BROWN
1-1/3 248610700 WHITE
2 248610800 ORANGE
3 248610900 BLUE
5 248611000 GREEN
7-1/2 248611300 BLACK-WHITE
10 248611200 RED-WHITE
15 248611500 RED-BLUE
Replacement
Safety Fuse
Cover
102774 ---
Replacement
Dummy Fuse
248872600 ---
Table 6
Bussmann GMT-Type Fuses
P/N 509128
GMT Fuse Module
Home