Application Guide

SAG582140000 System Application Guide
Issue AW, June 3, 2014 Spec. No. 582140000 (Models 802
NLDB, 802NLEB and 802NL-B)
Page 52 of 134
This document is property of Emerson Network Power, Energy Systems, North America, Inc. and contains confidential and proprietary information owned by Emerson Network Power, Energy
Systems, North America, Inc. Any copying, use, or disclosure of it without the written permission of Emerson Network Power, Energy Systems, North America, Inc. is strictly prohibited.
Bullet Nose-Type Circuit Breakers and Bullet Nose-Type Fuseholders e/w TLS/TPS Fuses
Distribution Only Bays
Features
Installs in the optional List C Fuse/Circuit Breaker Panel.
Load lugs are connected to busbars provided on the List C Fuse/Circuit Breaker Panel. These busbars
provide 1/4-20 threaded holes on 5/8" centers for installation of customer provided two-hole lugs. Load
return leads are terminated outside the bay to customer provided return busbars.
Each circuit breaker (as listed in Table 3 and Table 4) plugs into one, two, or three mounting position(s).
A single fuseholder provides for installation of a 3 to 100 ampere Bussmann TPS-type or Littelfuse
TLS-type fuse (as listed in Table 5). This fuseholder plugs into a single mounting position. This
fuseholder provides a GMT-A alarm type fuse, which operates open to provide an alarm indication if the
associated distribution fuse opens.
Restrictions
Load should not exceed 80% of device rating.
Caution: An overcurrent protective device with a rating of 150 amperes or greater SHALL HAVE an
empty mounting position between it and any other overcurrent protective device within the
List C Fuse/Circuit Breaker Panel.
Maximum size of wire to be connected to a single lug position is 2 AWG.
Maximum lug width is 0.610.
Customer must provide lug mounting bolts and additional hardware.
Bolt length: 3/4”.
Load return leads are terminated outside the bay to customer provided return busbars.
Ordering Notes
1) Order circuit breakers per Table 3 and Table 4.
2) Order fuses per Table 5. For each fuse ordered, also order one (1) P/N 117201 bullet nose type
fuseholder.
3) See Table 9 for recommended load distribution wire sizes and lugs.